Mitsubishi Electric MELSEC iQ-R Series User Manual page 93

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• To apply the offset/gain values set in one module to the other modules in the same system:
Ex.
When the offset/gain values in module No.1 are applied to modules No.2 to No.4
Methods for saving and restoring offset/gain values
The offset/gain values can be saved and restored by the following two types of operations.
• Saving and restoring by dedicated instructions
• Saving and restoring by reading from and writing to the buffer memory
■Saving and restoring by dedicated instructions
Use the dedicated instruction G(P).OGLOAD to temporarily save the offset/gain values of the source D/A converter module to
the internal device of the CPU, then use G(P).OGSTOR to write the values to the destination D/A converter module.
Prevent the saved offset/gain setting data from being deleted, by one of the following methods before replacing the modules:
• Use latch settings for the internal device of the destination module.
• Save the data onto an SD memory card. (To write data: use the SP.FWRITE instruction. To read data: use the SP.FREAD
instruction.)
• Store the saved data.
For use of dedicated instructions, refer to the following.
 MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
1.
Save the offset/gain values of module No.1.
2.
Apply the offset/gain values to modules No.2 to No.4.
1.18 Backing up, Saving, and Restoring Offset/Gain Values
1
1 FUNCTIONS
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dav8R60da4R60dai8

Table of Contents