Restrictions and precautions on the wave output function
The wave output function has the following restrictions and precautions.
■Output range setting
The user range cannot be used. When executing the wave output function, use the range other than the user range.
For the setting procedure of the output range, refer to the following.
Page 18 Range Switching Function
■Scaling function
The scaling function cannot be used when the wave output function is selected. When executing the wave output function,
disable the scaling function.
■Analog output HOLD/CLEAR function
The operation of the analog output HOLD/CLEAR function for the normal output differs from the operation for the wave output.
For details, refer to the following.
Page 20 In the wave output mode
■Remote head module
When the D/A converter module is mounted together with the remote head module, function blocks (FBs) cannot be used. To
execute the wave output function, refer to the following.
Page 58 Registering data when the remote head module is used
Wave data
The wave data indicate the time-series arrangement of the digital input values to be output in analog. Up to 80000 points can
be used. The wave data is registered in 'Wave data registry area' (Un\G10000 to Un\G89999).
1 FUNCTIONS
40
1.14 Wave Output Function