Mitsubishi Electric MELSEC iQ-R Series User Manual page 95

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Range reference table
The following describes the range reference tables used for saving and restoring offset/gain values.
■Factory default setting
The following describes the buffer memory addresses of the factory default setting.
R60DA4: 'CH1 Factory default setting offset value' (Un\G4004) to 'CH4 Factory default setting gain value' (Un\G4011)
R60DAV8, R60DAI8: 'CH1 Factory default setting offset value' (Un\G4004) to 'CH8 Factory default setting gain value'
(Un\G4019)
• For the R60DA4
Address (decimal)
CH1
CH2
CH3
4004
4006
4008
4005
4007
4009
*1 The reference values differ depending on the setting of 'Save data type setting' (Un\G4002) (voltage or current).
• For the R60DAV8
Address (decimal)
CH1
CH2
CH3
CH4
4004
4006
4008
4010
4005
4007
4009
4011
• For the R60DAI8
Address (decimal)
CH1
CH2
CH3
CH4
4004
4006
4008
4010
4005
4007
4009
4011
■User range setting
The following describes the buffer memory addresses of the user range setting.
R60DA4: 'CH1 User range setting offset value' (Un\G4012) to 'CH4 User range setting gain value' (Un\G4019)
R60DAV8, R60DAI8: 'CH1 User range setting offset value' (Un\G4020) to 'CH8 User range setting gain value' (Un\G4035)
Offset/gain value
*1
Voltage
0V
1V
5V
10V
Current
0mA
4mA
20mA
*1 This value is stored in User range setting offset value by default of the R60DAV8.
*2 This value is stored in User range setting gain value by default of the R60DAV8.
*3 This value is stored in User range setting offset value by default of the R60DA4 and R60DAI8.
*4 This value is stored in User range setting gain value by default of the R60DA4 and R60DAI8.
Description
CH4
4010
Industrial shipment
settings offset value
4011
Industrial shipment
settings gain value
CH5
CH6
CH7
4012
4014
4016
4013
4015
4017
CH5
CH6
CH7
4012
4014
4016
4013
4015
4017
*2
*3
*4
Save data type
Analog value
*1
setting
Voltage
0V
Current
0mA
Voltage
10V
Current
20mA
Description
CH8
4018
Industrial shipment settings
offset value
4019
Industrial shipment settings
gain value
Description
CH8
4018
Industrial shipment settings
offset value
4019
Industrial shipment settings
gain value
Reference value (hexadecimal)
Approx. 8000H
Approx. 8C80H
Approx. BE80H
Approx. FCFFH
Approx. 0B21H
Approx. 37A7H
Approx. E9BCH
1.18 Backing up, Saving, and Restoring Offset/Gain Values
Reference value
(hexadecimal)
Approx. 8000H
Approx. 0B21H
Approx. FCFFH
Approx. E9BCH
Analog value
Reference
value
(hexadecimal)
0V
Approx. 8000H
10V
Approx. FCFFH
Analog value
Reference
value
(hexadecimal)
0mA
Approx. 0B21H
20mA
Approx. E9BCH
1 FUNCTIONS
1
93

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dav8R60da4R60dai8