CH1 Alert output setting
Set whether to enable or disable the alert output.
For the alert output function, refer to the following.
Page 28 Alert Output Function
Setting value
0
1
If a value other than the above is set, an alert output setting range error (error code: 1B0H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alert output setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all channels.
Alert output setting [Q compatible mode]
When the Q compatible mode function is used, set whether to enable or disable the disconnection detection or alert output.
The following shows the setting details in the Q compatible mode.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Alert output enable, 1: Alert output disable
(2) b4 to b15 of the R60DA4 and b8 to b15 of the R60DAV8 and R60DAI8 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Disconnection detection/Alert output setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Alert output disable (1) for all channels.
CH1
CH2
508
708
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
CH2
47
Description
Enable
Disable
CH3
CH4
CH5
908
1108
1308
b1
b0
CH1
CH3
CH4
CH5
CH6
CH7
CH8
1508
1708
1908
CH6
CH7
CH8