Unlocking; Safety-Switch Setting 2 - ABB ACS580MV Hardware Manual

200 kw to 6300 kw, 6 kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

110 Maintenance
3
1
2
1
2
3
 

Unlocking

1. To access the release dial of the safety switch, remove the cap in the top right corner
of the INU compartment door.
2. Turn the release dial from the locked to the unlocked position.
PZ0
3. When the door is open, turn the release dial to the locked position.
4. Insert the cap again.

Safety-switch setting 2

1
2
3
1
2
3

Unlocking

1. To access the release dial of the safety switch, remove the cap in the top right corner
of the INU compartment door.
2. Screw out the locking screw (1) until the release dial can be turned.
Release dial
Unlocked position
The unlocked position enables opening the door of a medium voltage
unit whether the auxiliary voltage is switched on or off.
Locked position
Locked is the normal operating setting. To open the door of a medium
voltage unit, the DC link must be discharged and the auxiliary voltage
must be switched on.
 
Release dial
Unlocked position
The unlocked position enables opening the door of a medium voltage
unit whether the auxiliary voltage is switched on or off.
Locked position
Locked is the normal operating setting. To open the door of a medium
voltage unit, the DC link must be discharged and the auxiliary voltage
must be switched on.