46 Control system and interfaces
Fault
Default control connections for the factory macro
XPOW External power input
1
+24VI
GND
2
XA I
Reference voltage and analog inputs
1
+VREF
2
-VREF
AGND
3
4
AI1+
AI1-
5
6
AI2+
AI2-
7
Analog outputs
XA O
1
AO1
AGND
2
3
AO2
AGND
4
XRO1, XRO2, XRO3 Relay outputs
NC
11
COM
12
NO
13
21
NC
22
COM
NO
23
31
NC
COM
32
33
NO
Digital interlock
XD24
5
+24 VD
DICOM
6
7
+24 VD
DIOGND
8
XDIO
Digital input/outputs
DIO1
1
DIO2
2
Digital inputs
XDI
1
DI1
2
DI2
DI3
3
4
DI4
DI5
5
6
DI6
Control panel connection (internally used)
X13
X205
M emory unit connection (internally used)
PC ethernet connection for Drive Composer
XETH
24 VDC, 2 A (internally used)
10 VDC, R
1...10 kohm
L
-10 VDC, R
1...10 kohm
L
Ground
Speed reference
0(2)...10 V, R
>200 kohm
in
By default not in use.
0(4)...20 mA, R
>100 ohm
in
Motor speed rpm
0...20 mA, R
<500 ohm
L
Motor current
0...20 mA, RL<500 ohm
250 VAC/30 VDC
250 VAC/30 VDC
250 VAC/30 VDC
+24 V DC 200 mA
Digital input ground
+24 V DC 200 mA
Digital input/output ground
M CB trip command (internally used)
M CB status closed (internally used)
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Reset
Acc/Dec time set 1 (0) / set 2 (1)
Constant speed 1 (1 = On)
By default, not in use
Ready
2 A
Running
2 A
Fault (-1)
2 A