Nuts with bonded coating can be used as an alternative to uncoated stainless steel
nuts.
Connection type
The following connection type is recommended when connecting a cable lug (4) to a
busbar:
Spring washer (1) and flat washer (2) on each side of the busbar (3).
Other washers can be used, provided they maintain the required contact pressure.
1
5
1
Spring washer (2 pcs. per terminal)
2
Flat washers (2 pcs. per terminal)
3
Busbar
4
Cable lug
5
M12 bolt
6
M12 nut
Use cable lugs suitable for M12 bolts. The required tightening torque is 40 Nm.
Lubrication
If stainless steel bolts and nuts are used, lubricate the thread and head contact
surface of the bolt using recommended pasts, e.g. Molykote D paste.
Note: If a coated nut (e.g. with bonded molybdenum-disulfide [MoS
the connection does not have to be lubricated.
Tightening torque
Tighten bolted connections with bolts of sizes M10 and greater with the recommended
nominal torque for the bolt size used.
Installing auxiliary, control and serial communication
cables

Further information

See
ACS580MV Base frame & TEU layout design
Project-specific cable entry
1
2
3
2
4
Electrical installation 79