104 Maintenance
After the DC link capacitors have discharged completely, the cabinet doors of the
power compartments unlock, the SUPPLY OFF pushbutton changes to a permanent
light and the status line displays
4. Rack-out, lock-out, ground and tag-out the main power feeder.
5. Switch off and lock-out all auxiliary voltages from external sources.
6. Verify that the drive system is de-energized.
7. To connect a grounding set, continue with
8. To open the door of the medium voltage compartment, continue with
locking the doors
on page 104.
Tip: To open the power compartment doors, auxiliary voltage is required.
9. Before start working in the power compartment, the power modules must be
individually grounded by touching them with the grounding stick. See
power module with grounding hook

Unlocking and locking the doors

The door is secured by a safety switch and the control compartment door has pivoted door
handles and locks with triangular inserts. Open the door with the supplied key.
1. To release the door handle, insert and turn the key to the right. The door handle will
pop out.
2. To open the door, turn the door handle
to the right, if the door is hinged on the right,
to the left, if the door is hinged on the left.
3. To lock the door, bring the door handle in line with the door plate and press the handle
down until it clicks in.

Connecting a grounding set

Before starting to work on the drive, you must ground the three input and three output
terminals in the terminal unit (TEU). Always ground the drive on both sides, i.e. on supply
and motor side. Grounding on motor side is needed to avoid induced voltage from a
spinning rotor.
.
Connecting a grounding set
on page 107.
on page 104.
Unlocking and
Grounding