Storage; Storage Conditions; Preparing Cabinets For Storage; Storage And Handling Instructions For Spare Parts - ABB ACS580MV Hardware Manual

200 kw to 6300 kw, 6 kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

The forks must be at least as long as the cabinet.
Insert the fork fully into the cabinet's forklift pockets.

Storage

Storage conditions

The minimum requirements for storage are based on IEC 60721-3-1 'Classification of
environmental conditions: Classification of groups of environmental parameters and their
severities; Storage'.
Parameter
1K5 (climatic conditions), 1C2 (chemical gases), 1S2 (solid particles), 1M2 (vibration
and shock)
Low air temperature
High air temperature
Relative humidity
Cabinets can be stored for up to one year in the original packaging as long as they are not
damaged or opened. For information on longer storage periods, contact the ABB service
organization.

Preparing cabinets for storage

If the drive is taken out of service for a longer time proceed as follows:
1. Cover all cable inlets and ventilation slots with an impermeable plastic or aluminum foil
and a wooden panel.
2. Add a desiccant of the appropriate quality:
1 unit desiccant (30 g) absorbs 6 g water vapor.
The following quantity is needed when using a polyethylene foil:
2
10 units/m
foil
3. Close and lock the doors of the cabinet.
4. Use polyethylene or equivalent for packaging:
2
0,3 g/m
/24 h water vapor diffusion
5. Attach humidity indicators to the packaging.
Check the storage conditions and the packaging regularly. Immediately repair any
damages that occur during the storage period.

Storage and handling instructions for spare parts

Electronic devices (e.g, circuit boards, power modules) are sensitive to electrostatic
discharge (ESD). ESD can damage these devices.
Apply ESD handling precautions before handling these devices.
Check the spare parts immediately after receipt for damages. Report any damage to the
shipping company and the ABB service organization.
Transportation, storage and disposal 57
Limits
-40 °C
70 °C
5 to 85 %, no condensation

Hide quick links: