● The CBE20 can be assigned to IF1 or IF2 when SINAMICS Link is used.
The interface, assigned to the CBE20, must be switched into synchronous operation if
p8812[0] = 1 is set.
You must also make the following parameter settings in order to assign, e.g. IF1 to
SINAMICS Link:
– For IF1: p8839[0] = 2 (COMM BOARD)
– For IF2: p8839[1] = 1 (Control Unit onboard)
The data in the additional description are applicable for the case (IF1 ≙ SINAMICS Link).
● The number of the respective node must be entered manually in parameter p8836. Each
node must be assigned a different number. Enter the numbers in ascending order starting
with 1.
● If p8836 is set to 0, the nodes and the complete following line is shut down for SINAMICS
Link.
● Gaps in the numbering are not permitted, as then SINAMICS Link would not function.
● The node with the number 1 is automatically the sync master of the communication link.
● The ports of the CBE20 must be interconnected strictly in accordance with the above
diagram. You must always connect port 2 (P2) of node n with port 1 (P1) of node n + 1.
● In the "SINAMICS Link" mode, ports 3 and 4 of the CBE20 can only be used to connect to
the STARTER commissioning tool or Startdrive.
Corresponding parameters for IF1 or IF2
Use different parameters for configuring, depending on which interface SINAMICS Link is
assigned:
Table 11- 54 Corresponding parameters
Parameters
Setting of the processing mode for PROFIdrive STW1.10 "Control by
PLC".
Connector output to interconnect the PZD (setpoints) received from the
fieldbus controller in the word format.
Selects the PZD (actual values) to be sent to the fieldbus controller in
the word format.
Displays the PZD (actual values) sent to the fieldbus controller in the
word format.
Connector output to interconnect the PZD (setpoints) received from the
fieldbus controller in the double word format.
Selects the PZD (actual values) to be sent to the fieldbus controller in
the double word format.
Displays the PZD (actual values) sent to the fieldbus controller in the
double word format.
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.6 Communication via SINAMICS Link
IF1
p2037
r2050
p2051
r2053
r2060
p2061
r2063
Communication
IF2
p8837
r8850
p8851
r8853
r8860
p8861
r8863
891