Preconditions for PN Gate

Hardware
● SINAMICS CU320-2 PN with firmware version as of 4.5
● Communication Board Ethernet 20 (CBE20)
● Short Ethernet cable to connect CBE20 and CU320-2 PN (X150)
Recommendation: Ethernet cable with the article number: 6SL3060-4AB00-0AA0
● Control hardware with standard Ethernet interface (100 Mbit/s or higher),
for example, the SIMATIC Box IPC 427C.
Note
The Gate PC must guarantee the short latency times required for operating the PN Gate.
Influencing variables are the CPU performance, mainboard hardware (Ethernet chipset and
its connection), and the BIOS and the software components involved (operating system
components such as memory mapping, Ethernet driver, interrupt link, configuration).
Software
● STARTER as of V4.3
or
● Drive ES as of V5.5
or
● SIMATIC STEP 7 as of V5.5 SP2
● Development kit for the development and configuration:
– SINAMICS PN Gate DevKit (Article No. 6SL3071-0CA00-0XA0)
● Licenses
– The PN Gate CU requires a runtime license with Article No. 6SL3074-0AA03-0AA0 or
PROFINET version
● SINAMICS PN Gate V2 is compatible with PROFINET V2.2
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
the Z option G01 for CFC.