Siemens SINAMICS S120 Function Manual page 773

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Data sets DS0/DS1 and diagnostics alarm
The PROFIdrive message classes are transferred using diagnostic alarm DS0/DS1. All faults
are assigned channel 0. The drive objects are assigned using the slot number.
The structure is as follows:
Bit
Octet
Name
1
Header-Byte
2
3
4
5
DS0 (byte 0)
6
DS0 (byte 1)
7
DS0 (Byte 2)
8
DS0 (byte 3)
9
Info (byte 1)
10
Info (byte 2)
11
Info (byte 3)
12
Channel Error
Vector
13
Channel
-related diag-
14
nostics
15
(channel 0)
Alarm_Specifier
1)
1 ≙ error has occurred and the slot is not OK
2 ≙ error is resolved and the slot is OK
3 ≙ error is resolved and the slot is not okay
Channel fault present
2)
= 1; as long as the drive object has an error condition
Internal fault
3)
= 1; as long as the drive object has an error condition
Module fault
4)
= 1; as long as the drive object has an error condition
Channel information present
5)
= 1; ≙ DS1 exists
Type class of module
6)
= 0011; ≙ Distributed
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
7
6
0
0
0
0 ... 31 (sequence number)
0
0
0
0
0
0
0
0
Mixed
0
0
Err 7
Err 6
Err 15
Err 14
Err 13
0
0
11.1 Communication according to PROFIdrive
5
4
= 15 (block length)
= 1 (diagnostics alarm)
0 ... 244 (slot number ≙ drive object)
0
0
0
1
5)
0
0
0
0
= 0x45 (ChannelTypeID = SINAMICS)
= 24 (number of diagnostic bits/channel)
= 1 (1 channel signals)
0
0
Err 5
Err 4
Err 3
Err 12
Err 11
0
0
Err 19
3
2
Add_Ack
Alarm_Specifier
1
0
1
2)
0
0
1
6)
6)
0
0
0
0
0
0
Err 2
Err 1
Err 10
Err 9
Err 18
Err 17
Communication
1
0
1)
1
3)
4)
1
6)
6)
0
0
0
0
0
Channel 0
1
Err 0
Err 8
Err 16
773

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents