(2)
Three-wire type (STF, STR, STOP signal)
 The three-wire connection is shown below.
 Turning the STOP signal ON makes start self-holding function valid. In this case, the forward/reverse rotation signal
functions only as a start signal.
 If the start signal (STF or STR) is turned ON and then OFF, the start signal is held and makes a start. When changing the
direction of rotation, turn STR (STF) ON once and then OFF.
 To stop the drive unit, turning off the STOP signal once decelerates it to a stop.
 When using the STOP signal, set "25" in Pr.178 to Pr.184 to assign function.
Forward
Stop
rotation start
Reverse
rotation start
Forward
rotation
Reverse
rotation
ON
STF
STR
STOP ON
3-wire connection example (Pr.250 = "9999")
REMARKS
 When the JOG signal is turned ON to enable Jog operation, the STOP signal becomes invalid.
 If the MRS signal is turned ON to stop the output, the self-holding function is not canceled.
NOTE
 Under position control, the three-wire type is not available.
(3)
Start signal selection
STF
STR
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)
Pr.178 to Pr.184 (input terminal function selection)
Function assignment of external terminal and control
STF
Drive unit
STR
STOP
SD
Time
ON
OFF
OFF
Pr.250 Setting Drive Unit Status
0 to 100s, 9999
Stop
Reverse rotation
Forward rotation
Stop
Refer to page 117
Refer to page 138
Stop
Start
Forward rotation
/reverse rotation
Forward
rotation
Reverse
rotation
ON
STF
ON
STR
STOP ON
OFF
3-wire connection example (Pr.250 = "8888")
1000s to 1100s, 8888
Stop
Forward rotation
Reverse rotation
STF
Drive unit
STOP
STR
SD
Time
ON
OFF
143
4