Operation panel I/O terminal monitor (Pr.52)
When Pr.52 is set to "55", the I/O terminal status can be monitored on the operation panel.
The I/O terminal monitor is displayed on the third monitor.
The LED is ON when the terminal is ON, and the LED is OFF when the terminal is OFF. The center line of LED is always
ON.
On the unit I/O terminal monitor (Pr.52 = "55"), the upper LEDs denote the input terminal status and the lower the output
terminal status.
RM
RH
RL
RUN
ABC
(4)
Cumulative power monitor and clear (Pr.170)
On the cumulative power monitor (Pr.52 = "25"), the output power monitor value is added up and is updated in 100ms
increments. (The values are saved in EEPROM every hour.)
The operation panel, parameter unit (FR-PU07) and communication (RS-485 communication, communication option)
display increments and display ranges are as indicated below.
Operation Panel
Range
Unit
0 to 99.99kWh
0.01kWh
100.0 to 999.9kWh
0.1kWh
1000 to 9999kWh
1kWh
Power is measured in the range 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
Power is measured in the range 0 to 99999.99kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in 0.1kWh increments.
Writing "0" to Pr.170 clears the cumulative power monitor.
REMARKS
If "0" is written to Pr.170 and Pr.170 is read again, "9999" or "10" is displayed.
Monitor display and monitor output signal
RES
STF
MRS
STR
FU
Parameter Unit
Range
0 to 999.99kWh
1000.0 to 9999.9kWh
10000 to 99999kWh
Input terminal
Center line is always ON
Output terminal
Communication
Range
Unit
Pr.170 = 10
0.01kWh
0.1kWh
0 to 9999kWh
1kWh
- Display example -
When signals STF, RH and
RUN are ON
Hz
A
V
Unit
Pr.170 = 9999
0 to 65535kWh
1kWh
(initial value)