Remote Setting Function (Pr.59) - Mitsubishi Electric FR-E700EX Instruction Manual

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

Speed setting by external terminals
NOTE
 The Pr.15 setting should be equal to or higher than the Pr.13 Starting speed. If "0r/min" is set in Pr.15 under position
control, no position command is created and the stop state remains.
 The JOG signal (JOG2 signal) can be assigned to the input terminal using any of Pr.178 to Pr.184 (input terminal function
selection). When terminal assignment is changed, the other functions may be affected. Set parameters after confirming
the function of each terminal.
 During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 141))
 When Pr.79 Operation mode selection = "4", pressing
(FR-PU07) starts the drive unit and pressing
 This function is invalid when Pr.79 = "3".
Parameters referred to
 Pr.29 Acceleration/deceleration pattern selection
 Pr.20 Acceleration/deceleration reference speed
 Pr.79 Operation mode selection
 Pr.178 to Pr.184 (input terminal function selection)
4.8.3

Remote setting function (Pr.59)

 Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous
variable-speed operation, without using analog signals.
 By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the
motorized speed setter (FR-FK).
Parameter
number
59
Remote function selection
The above parameter can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)
Drive unit
Forward rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection diagram
for remote setting
122
Refer to page 125
Refer to page 186
Name
Initial value
0r/min
0
Acceleration
ON
(RH)
Deceleration
(RM)
Clear (RL)
Forward rotation
(STF)
Power supply
 External running speed (other than multi-speed) or PU running speed
of the operation panel and
stops the drive unit.
Refer to page 129
Refer to page 138
Setting
RH, RM, RL signal
range
0
Multi-speed setting
1
Remote setting
2
Remote setting
0
3
Remote setting
ON
ON
ON
ON
/
of the parameter unit
Description
Speed setting
function
storage function
Not used
(Turning the power OFF
clears remotely-set speed.)
Not used
(Turning the power OFF or
STF/STR OFF clears
remotely-set speed.)
When Pr.59 =1
When Pr.59 =1, 2
When Pr.59 =3
When Pr.59 =2, 3
ON
ON
ON
ON
With
Time
ON
ON