Mitsubishi Electric FR-E700EX Instruction Manual page 201

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

(5)
Selection of command source in Network operation mode (Pr.338, Pr.339)
 There are two control sources: operation command source, which controls the signals related to the drive unit start
command and function selection, and speed command source, which controls signals related to speed setting.
 In Network operation mode, the commands from the external terminals and communication (PU connector or
communication option) are as listed below.
Pr.338 Communication operation
Operation
command source
Location
Pr.339 Communication speed
Selection
command source
Fixed
Running speed from
function
communication
(terminal-
Terminal 2
equivalent
Terminal 4
function)
Low-speed operation
0
RL
command/remote setting
clear
Middle-speed operation
1
RM
command/remote setting
function
High-speed operation
2
RH
command/remote setting
function
3
RT
Second function selection
4
AU Terminal 4 input selection
5
JOG Jog operation selection
External thermal relay
7
OH
input
8
REX 15-speed selection
10
X10 Drive unit run enable signal
PU operation external
12
X12
interlock
14
X14 PID control valid terminal
PU/External operation
16
X16
switchover
23
LX
Pre-excitation
Output stop
24
MRS
PU operation interlock
25 STOP Start self-holding selection
29
X29 Stopper control switchover
30 JOG2 Jog operation selection 2
44
X44 P/PI control switchover
60
STF Forward rotation command
61
STR Reverse rotation command
62
RES Drive unit Reset
PU/NET operation
65
X65
switchover
External/NET operation
66
X66
switchover
Command source
67
X67
switchover
76
X76 Proximity dog
86
SON Servo-ON
87
X87 Position control sudden stop
88
LSP Forward stroke end
89
LSN Reverse stroke end
[Explanation of table]
External
: Command is valid only from control terminal.
NET
: Command only from communication is valid
Combined : Command from both control terminal and communication is valid.
: Command from either of control terminal and communication is invalid.
REMARKS
 The command source of communication is as set in Pr.550 and Pr.551.
 The Pr.338 and Pr.339 settings can be changed while the drive unit is running when Pr.77 = "2". Note that the setting change is
reflected after the drive unit has stopped. Until the drive unit has stopped, communication operation command source and
communication speed command source before the setting change are valid.
Selection of operation mode and operation location
0: NET
0: NET 1: External 2: External 0: NET 1: External 2: External
NET
NET
External
External
NET
External
NET
External
NET
External
NET
Combined
NET
External
NET
External
NET
Combined
NET
NET
NET
NET
NET
Combined
NET
Combined
Combined
Combined
1: External
NET
NET
External
External
NET
External
NET
External
NET
External
External
Combined
External
External
NET
External
External
External
NET
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
External
Remarks
Pr.59 = "0"
(multi-speed)
Pr.59 = "1, 2"
(remote)
Pr.59 = "0"
(multi-speed)
Pr.79  "7"
Pr.79 = "7"
When the X12
signal is not
assigned
4