4.13 Monitor display and monitor output signal

Purpose
To display motor speed
To set speed
To change PU monitor display data
To change the monitor output from
terminal FM
To set the reference of the monitor
output from terminal FM
To adjust terminal FM outputs

4.13.1 Speed display and speed setting (Pr.37, Pr.144)

The increments of the motor speed and the monitored items displayed on the operation panel and PU (FR-PU07) can
be switched among frequency, machine speed, etc.
Parameter
Name
number
37
Speed display
Speed setting
144
switchover
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)

The maximum value of the setting range differs according to the Pr.1 Maximum setting and it can be calculated from the following formula.
Maximum setting value of Pr.37
Note that the maximum setting value of Pr.37 is 9998 if the result of the above formula exceeds 9998.
 To display a machine speed, set the machine speed at 3000r/min in Pr.37, and set the number of motor poles (2, 4, 6, 8, 10)
in Pr.144.
For example, when Pr.37 = "1000", "1000" is displayed on the speed and set speed monitor when the running speed is
3000r/min. When running speed is 1500r/min, "500" is displayed.
 When the number of motor poles +100 (102, 104, 106, 108, 110) is set in Pr.144, values are displayed in motor speed
increments. (When Pr.37 = "0")
 To change the display increments to frequency, set the number of motor poles (10) in Pr.144. (When Pr.37 = "0")
 A combination of the Pr.37 and Pr.144 settings determines the monitored item and the setting increment as shown in the
table below. (Initial settings are outlined with bold borders)
Pr.37 setting
Pr.144 setting value
value
2 to 10
0 (initial value)
102 to 110 (initial value)
2 to 10
0.01 to 9998
102 to 110
 Motor speed r/min conversion formula............... frequency
Machine speed conversion formula..................... Pr.37
For Pr.144 in the above formula, the value is "Pr.144-100" when "102 to 110" is set in Pr.144.
Monitor display and monitor output signal
Speed display and speed setting
DU/PU main display data selection
Cumulative monitor clear
Terminal FM function selection
Terminal FM standard setting
Terminal FM calibration
Initial
value
0
0.75K or lower
110
2, 4, 6, 8, 10, 102, 104,
1.5K, 2.2K
104
3.7K
106
16777.215  3000r/min
<
Setting value of Pr.1 (r/min)
Output frequency
monitor
0.01Hz
1r/min
0.001
(Machine speed
)
0.01Hz

120/number of motor poles (Pr.144)
speed/3000r/min
Parameter to set
Pr.52, Pr.54, Pr.170, Pr.171,
Pr.268, Pr.563, Pr.564
Setting range
0
Rotation speed display, setting
0.01 to 9998
Machine speed at 3000r/min.

Set the number of motor poles when
106, 108, 110
displaying the frequency.
Set frequency
Frequency setting
monitor
0.01Hz
0.01Hz
1r/min
1r/min
0.001
0.001
(Machine speed
)
(Machine speed
0.01Hz
0.01Hz
Refer to
page
Pr.37, Pr.144
153
155
Pr.54
155
Pr.55, Pr.56
161
Pr.900
162
Description
Parameter setting
0.01Hz
1r/min
0.01Hz
)
0.01Hz
153
4