Meaning Of The Leds On The Motor Module Booksize Compact - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

6.3.7

Meaning of the LEDs on the Motor Module Booksize Compact

Table 6- 5
LEDs on the Single Motor Module / Double Motor Module
Status
Ready (H200) DC link (H201)
OFF
OFF
Green
OFF
Orange
Red
Orange
Orange
Red
Green / Red
(0.5 Hz)
Green / Red
-
(2 Hz)
Green /
Orange
or
Red / Orange
Hazardous DC link voltages may be present at any time regardless of the status of the "DC
link" LED.
The warning information on the components must be carefully observed!
SINAMICS S120 Combi
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0
Electronics power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component recognition via LED is activated (p0124).
Note:
Both options depend on the LED status when
component recognition is activated via p0124 = 1.
DANGER
Motor Modules Booksize Compact as expansion axes
Description, cause
6.3 Interface description
Remedy
Check the line supply
voltage.
Remedy and acknowledge
fault
Carry out a POWER ON
133

Advertisement

Table of Contents
loading