X533 Digital Outputs - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

9.1.3.13

X533 digital outputs

Table 9- 12
Screw terminal X533
Terminal
1
2
3
An F-DO comprises two digital outputs and a digital input for the feedback signal
F-DO 2 = terminals 1, 2 and 3
Max. connectable cross-section: 1.5 mm²
Type: Screw terminal 1 (see Chapter "Control cabinet installation and EMC / connection system")
1) DI: Digital input; DO: Digital output
2) Pure hardware delay
SINAMICS S120 Combi
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0
Designation
1)
DI 22
DO+
DO-
Additional system components
9.1 Terminal Module TM54F
Technical specifications
Voltage: - 3 V to +30 V
Typical current consumption: 3.2 mA at 24 V DC
Electrical isolation: Reference potential is terminal M1
The digital input is electrically isolated.
Input delay:
2)
- for "0" to "1": 30 μs (100 Hz)
- for "1" to "0": 60 μs (100 Hz)
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
0.5 A
Reference potential is terminal M1
0.5 A
Reference potential is terminal L1+, L2+ or L3+
Output delay:
2)
- for "0" to "1": 300 μs
- for "1" to "0": 350 µs
Total current consumption of all DOs: 2 A
Max. leakage current: < 0.5 mA
Switching frequency:
For resistive load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: Max. 10 Hz
Maximum lamp load: 5 W
187

Advertisement

Table of Contents
loading

Table of Contents