Siemens SINAMICS S120 Combi Equipment Manual page 48

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Line-side power components
2.8 Line connection versions
A matching transformer must be dimensioned for the total of all loads connected to it. The
apparent powers required must be determined and added as indicated in the table titled
"Transformer configuration instructions". If the transformer is too small (S
lead to increased line voltage dips and faults in the line supply and in other loads at this
connecting point.
If other loads are connected to the secondary side of the matching transformer, the boundary
conditions indicated under a) and b) must be followed when selecting the matching
transformer.
S
, S
n1
u
= short-circuit voltage of the matching transformer in %
k
(must be between 1% and 3% for the S120 Combi)
S
= short-circuit power.
K
A sufficiently high system fault level (short-circuit power) is required to ensure that when a
fault does occur, the fuses rupture in the specified time. An insufficient system fault level
(short-circuit power) increases the time to trip beyond permissible levels (e.g. a fire is
possible).
Boundary condition a) Rated power
The rated power of the matching transformer S
the rated power P
S
n1
Example:
The minimum rated power of a matching transformer for a 16 kW S120 Combi Power
Module is 21 kVA.
Boundary condition b) Short-circuit power
In order to avoid faults and disturbances at the other loads that are connected to the
secondary side of the matching transformer, the total short-circuit power of the plant
connection and that of the matching transformer at the connection point must reach the
following values:
S
K line
Special case:
During operation with only one supply at a transformer, the values may be reduced by the
factor 0.73.
S
K line
For example S
From S
48
= calculated rated power of the transformer resulting from a) and b)
n2
WARNING
of the S120 Combi Power Module.
n
≥ 1.27 • P
n
≥ 70 • P
n
≥ 0.73 • 70 • P
n
for 16 kW S120 Combi Power Module: S
K line
the required rated power of the matching transformer can be calculated.
K transformer
must always be a factor of 1.27 higher than
n1
= 0.82 MVA = 820 kVA
K line
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0
or S
), this can
n
k
SINAMICS S120 Combi