DC link components
7.1 Braking Module
Note
Applying a high signal to terminal X21.1 inhibits the Braking Module. On a falling edge,
pending error signals are acknowledged.
The pre-warning for I*t monitoring is output as a high level on reaching 80 % of the maximum
braking resistor ON time.
Only braking resistors approved by Siemens for this component are identified automatically.
7.1.3.5
Meaning of the LEDs on the Braking Module
Table 7- 3
Meaning of the LEDs on the Braking Module
LED
Color
-
Green
READY
Red
DC LINK
-
Green
Note
To protect the braking resistor, the current fault cannot be acknowledged until after a waiting
period of approx. 3 min after an I*t shutdown of the braking module.
150
Status
Description
Off
Electronics power supply outside the permissible tolerance range.
Continuous
The component is ready for operation.
light
Braking Module inhibited via DI X21.1
Continuous
•
light
Braking Module shutdown
•
Possible reasons:
–
Overcurrent
–
Overtemperature heat sink
–
Braking resistor overload (I*t shutdown)
Off
Braking resistor switched off (DC link discharge not active)
Flashing
Braking resistor switched on (DC link discharge active)