Operating condition setting completed flag
Common
When changing values of the buffer memory, use 'Operating condition setting completed flag' (X9) as an interlock condition to
turn on and off 'Operating condition setting request' (Y9). For the buffer memory areas that require turning on and off of
'Operating condition setting request' (Y9) to enable the new values, refer to the following.
Page 146 List of buffer memory areas
When 'Operating condition setting request' (Y9) is on, 'Operating condition setting completed flag' (X9) turns off.
'Module READY' (X0)
'Operating condition setting
completed flag' (X9)
'Operating condition setting
request' (Y9)
Performed by the D/A converter module
Performed by a program
■Device number
The following shows the device number of this input signal.
Signal name
Operating condition setting completed flag
APPX
138
Appendix 2 I/O Signals
ON
ON
CH1
X9
ON
OFF
ON
OFF
CH2
CH3
CH4