CH1 Input value shift amount
Normal
Set the shift amount you want to shift to 'CH1 Digital value' (Un\G460). The set value is added to the digital value regardless
of the on/off state of 'Operating condition setting request' (Y9).
For details on the shift function, refer to the following.
Page 31 Shift Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Input value shift amount
■Setting range
The setting range is from -32768 to 32767.
■Default value
The default value is 0 for all channels.
CH1 Wave step action movement amount
Wave
This area is for setting wave output step action movement amount and for checking if the movement has been completed.
The value of wave data in the wave data registry area (Un\G10000 to Un\G99999) that is outputting in analog is moved to
wave data in the buffer memory address that is obtained by adding or subtracting the set value. When a value is set in this
area, the target address starts to be specified and when specifying the address is complete, No movement (0) is stored.
This area can be set only when the following conditions are satisfied.
• In the wave output mode
• During wave output step action (3) is stored in 'CH1 Wave output status monitor' (Un\G401).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave step action movement amount
■Setting range
• Setting range: -30000 to 30000
• Set the following value according to the direction to move.
Movement direction
No movement
Forward movement (movement in address increasing direction)
Reverse movement (movement in address decreasing direction)
• The following shows the available range for movement.
Wave pattern
start address
• Even if a value set is outside the above range, no error occurs. When a value smaller than -30000 is set, the value is
processed as -30000. When a value greater than 30000 is set, the value is processed as 30000.
• When a value greater than the wave pattern data point is set, only the value for the wave pattern data point is processed.
■Default value
The default value is No movement (0) for all channels.
APPX
168
Appendix 3 Buffer Memory Areas
Wave pattern
to
start address
CH1
CH2
480
680
CH1
CH2
482
682
Setting value
0
1 to 30000
-30000 to -1
Wave pattern
+
data points
CH3
880
CH3
882
-
1
CH4
1080
CH4
1082