■For CLEAR setting
When the CPU module status is changed from RUN to STOP, the wave output is finished and the offset value is output. When
the CPU module status is changed from STOP to RUN, the value is output according to the setting in 'CH1 Output setting
during wave output stop' (Un\G524). The wave output does not restart.
To execute the wave output again, set 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request (0) after
changing the CPU module status from STOP to RUN. Then, change the value in 'CH1 Wave output start/stop request'
(Un\G462) from Wave output stop request (0) to Wave output start request (1).
CPU module status
'CH1 D/A conversion
enable/disable
setting' (Un\G500)
'CH1 Output enable/disable
flag' (Y1)
'CH1 Wave output start/stop
request' (Un\G462)
'CH1 Wave output status
monitor' (Un\G401)
Wave data
Output according to the setting of
'CH1 Output setting during wave
output stop' (Un\G524)
(1) The wave output stops.
(2) The offset value is output.
(3) The wave output does not restart.
(4) Setting 'CH1 Wave output start/stop request' (Un\G462) from Wave output stop request (0) to Wave output start request (1) starts the wave output.
RUN
D/A conversion enable (0)
OFF
Wave output stop
request (0)
During wave
output stop (0)
During
wave
Analog output
output (1)
Offset value
STOP
ON
Wave output start
Wave output stop
request (1)
request (0)
During wave
output stop (0)
(1)
(3)
(2)
RUN
Wave output start
request (1)
During wave
output (1)
(4)
1 FUNCTIONS
1.14 Wave Output Function
1
73