8.
Click [Close with Reflecting the Setting] button and close the "CC IE Field Configuration" window.
9.
Set "Refresh Setting" of the module parameter of the master/local module as shown below.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Refresh Setting]
[Detailed Setting]
10.
Click the [Apply] button.
11.
Write the set parameters to the CPU module on the master station. Then reset the CPU module or turn off and on the
power.
[Online] [Write to PLC]
For parameters of the master/local module which are not described in this procedure, set default values. For
details on parameters of the master/local module, refer to the following.
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)