CH1 Set value check code
Normal
When a set digital value is out of the setting range, a check code is stored.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Set value check code
■Check target
The check target varies depending on the operation mode.
Operation mode
Normal output mode
Wave output mode
Inter-module synchronization mode
*1 The buffer memory addresses in which digital values outside the setting range have been registered can be checked in the following:
'CH1 Wave output digital value outside the range address monitor' (Un\G440, Un\G441) (Page 165 CH1 Wave output digital value
outside the range address monitor)
■Stored check codes
Check code
000FH
00F0H
00FFH
Once the check code is stored, the code is not reset even when the digital value falls within the setting range.
When the scaling function is used, the value of 'CH1 Digital value' (Un\G460) which has undergone a scale conversion is
checked. Note that some errors may be observed in the target digital value for a check code to be stored due to the
calculation error of scale conversion when a scale-converted value exceeds the setting range.
■Resetting the check codes
Set a digital value within the setting range and turn on and off 'Error clear request' (YF).
CH1 Wave output status monitor
Wave
The status of a wave output can be checked for each channel.
Monitored value
0
1
2
3
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave output status monitor
APPX
162
Appendix 3 Buffer Memory Areas
Wave
Synchronization
CH1
400
Check target
'CH1 Digital value' (Un\G460)
Wave data registry area (Un\G10000 to Un\G99999)
'CH1 Synchronization digital value' (Un\G9500)
Description
A digital value exceeding the setting range has been written.
A digital value falling short of the setting range has been written.
A digital value falling short of the setting range and a digital value exceeding the setting range have been written.
This check code may be stored when a check code is not reset.
CH1
401
CH2
600
*1
Description
During wave output stop
During wave output
Wave output pause
During wave output step action
CH2
601
CH3
CH4
800
1000
CH3
CH4
801
1001