When a disconnection is detected
When a disconnection is detected during the wave output, the wave output status of the channel where the disconnection was
detected becomes the during wave output stop (the wave output stops). The wave output does not automatically restart even
after the recovery from the disconnection.
To restart the wave output, follow the procedure below.
1.
Set 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request (0).
2.
Eliminate the cause of the disconnection to restore the connection.
3.
Turn on and off 'Error clear request' (YF).
4.
Check the status of the module and external devices.
5.
Change the value in 'CH1 Wave output start/stop request' (Un\G462) from Wave output stop request (0) to Wave output
start request (1).
Wave output start/stop request cannot be accepted during disconnection.
Status of disconnection
Status of the CPU module
'CH1 Output enable/disable
flag' (Y1)
'Error clear request' (YF)
'CH1 D/A conversion
enable/disable
setting' (Un\G500)
'CH1 Wave output start/stop
request' (Un\G462)
'CH1 Wave output status
monitor' (Un\G401)
Wave data
'Output according to the
setting of 'CH1 Output
setting during wave
output stop' (Un\G524)
(1) 0V/0mA is output in analog.
(2) When a disconnection is detected, wave output stops.
(3) Since a disconnection was detected and the wave output has stopped, change 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request
(0).
(4) The wave output does not restart even after the recovery from the disconnection.
(5) To restart the wave output, turn on and off 'Error clear request' (YF). After that, change 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop
request (0), and then change it to Wave output start request (1) again.
1 FUNCTIONS
76
1.14 Wave Output Function
Not detected
RUN
OFF
ON
OFF
D/A conversion
enable (0)
Wave output
Wave output
stop request (0)
start request (1)
During wave
output stop (0)
Analog output
Offset value
0V/0mA
Detected
(3)
During wave
During wave
output (1)
output stop (0)
(2)
(1)
Restored
ON
Wave output
stop request (0)
(4)
(5)
OFF
Wave output
start request (1)
During wave
output (1)