Mitsubishi Electric MELSEC iQ-R Series User Manual page 186

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Offset/gain setting mode
Normal
Specify the channel where the offset/gain setting is adjusted.
• Offset/gain setting mode (offset specification): Channel where the offset value is adjusted
• Offset/gain setting mode (gain specification): Channel where the gain value is adjusted
Setting value
0
1
Set one of the offset specification or gain specification to Setting channel (1), and the other to Disable (0). When a value other
than 0 and 1 is set, an offset/gain setting channel range error (error code: 1E8H) occurs.
Multiple channels cannot be set at the same time.
In the following cases, an offset/gain setting channel specification error (error code: 1E50H) occurs.
• When both the offset specification and gain specification are set to Setting channel (1) at the same time
• When both the offset specification and gain specification of all channels are set to Disable (0)
• When multiple channels are set to Setting channel (1) at the same time
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Offset/gain setting mode (offset specification)
CH Offset/gain setting mode (gain specification)
■Enabling the setting
Turn on 'Channel change request' (YB).
■Default value
The default value is Disable (0) for all channels.
APPX
184
Appendix 3 Buffer Memory Areas
Description
Disable
Setting channel
CH1
CH2
4132
4134
4133
4135
CH3
CH4
4136
4138
4137
4139

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dah4

Table of Contents