Setting method
Set "Analog output HOLD/CLEAR setting" to "HOLD" or "CLEAR".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Output mode
setting function]
Precautions for when the remote head module has been mounted
When the D/A converter module has been mounted with the remote head module, set whether to hold or clear the analog
output value that has been output when the own station is disconnected with "CPU error output mode setting" of the module
parameter.
The following describes the settings required for using "CPU error output mode setting".
• Enable the station-based block data assurance for cyclic data on the sending side.
• To hold the analog output value, set "CPU error output mode setting" to "Hold". The analog output HOLD/CLEAR function
setting is disabled.
This setting is enabled module by module. Setting by each channel is not available. To match the output status of when a stop
error occurs or the CPU module is in the STOP state and that of when the own station is disconnected, set "Analog output
HOLD/CLEAR setting" to the same value in all the channels.
Operating status
The analog output value is held.
The analog output value is cleared.
(The offset value is output.)
*1 CPU error output mode setting is enabled in the following cases.
 When the own station is disconnected due to a network error
 When the data link is stopped by the CC-Link IE Field Diagnostics of the engineering tool
CPU error output mode setting
Hold
Clear
*1
Analog output HOLD/CLEAR setting
(Set the same value in all the channels.)
HOLD
CLEAR
1.5 Analog Output HOLD/CLEAR Function