CH1 D/A conversion enable/disable setting
Common
Set whether to enable or disable the D/A conversion.
For details on the D/A conversion enable/disable setting function, refer to the following.
Page 22 D/A Conversion Enable/Disable Setting Function
Setting value
0
1
When a value other than the above is set, the value is processed as D/A conversion disable (1).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH D/A conversion enable/disable setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is D/A conversion disable (1) for all channels.
CH1 Scaling enable/disable setting
Normal
Set whether to enable or disable the scaling.
For details on the scaling function, refer to the following.
Page 28 Scaling Function
Setting value
0
1
If a value other than the above is set, a scaling enable/disable setting range error (error code: 1A0H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling enable/disable setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is Disable (1) for all channels.
Description
D/A conversion enable
D/A conversion disable
CH1
CH2
500
700
Description
Enable
Disable
CH1
CH2
502
702
CH3
CH4
900
1100
CH3
CH4
902
1102
APPX