CH1 Wave pattern start address setting
Wave
This area is for setting the start address of the wave pattern to be output. The digital value in the buffer memory address set in
this area is the first target for D/A conversion. Subsequently, the successive values are converted to analog and output in turn.
For this area, set a value in 32-bit signed binary.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave pattern start address setting
■Setting range
• The setting range is from 10000 to 99999. Set an address within the range of the buffer memory addresses of Wave data
registry area (Un\G10000 to Un\G99999).
• In the channel where a value out of the setting range is set, a wave pattern start address setting range error (error code:
1D4H) occurs. The wave output does not start.
• Set the value so that the setting value in this area + 'CH1 Wave pattern data points setting' (Un\G528, Un\G529) - 1 is
99999 (the last address of wave data registry area) or less. In the channel where the value is over 99999, a wave data
registry area setting range error (error code: 1D9H) occurs. The wave output does not start.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 10000 for all channels.
APPX
176
Appendix 3 Buffer Memory Areas
CH1
CH2
526, 527
726, 727
CH3
CH4
926, 927
1126, 1127