861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
Risk of injury while transporting the voltage transformer
The voltage transformer may fall down during transport. Serious injury and property
damage can be the consequence.
➭ Secure the voltage transformer against falling down. If required, use a support.
➭ If necessary, transport the voltage transformer with several persons or with suitable aids.
➭ Lower the primary terminal of the voltage transformer slowly onto the panel connection
housing.
Fig. 136: Setting down the voltage transformer
Disruptive discharges due to air inclusions
Will damage the cast-resin bushing.
➭ While installing the voltage transformer, let excess air out of the plug-in connection with
a cable strap.
➭ Verify intact condition of the cable strap. If the cable strap was damaged when it was
pulled out, remove the voltage transformer and eliminate the residues of the cable strap.
➭ To let excess air out of the plug connection while mounting the voltage transformer,
fit a nylon thread or a cable strap into the inside cone of the panel connection cover.
➭ Insert the primary terminal of the voltage transformer slowly into the inside cone of the
panel connection cover, pulling the cable strap out at the same time.
➭ Fit plain washers on the threaded rods of the fixing bracket stecken. Bolt the voltage
transformer uniformly together with the panel connection cover using the M10 nuts.
Tightening torque: 30 Nm.
Fig. 137: Bolting the voltage transformer together
➭ Connect the low-voltage plug connector to the voltage transformer.
WARNING
Cable strap
CAUTION
Installation
115/214