Siemens 8DA10 Series Installation And Operating Instructions Manual page 177

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

1
Initial situation
3
Switch the left-hand three-position disconnector to OPEN position
(insert the operating lever for the DISCONNECTING function and turn
180° counter-clockwise).
5
Push the right-hand control gate to the left.
7
Remove the operating lever for the DISCONNECTING function.
The right-hand control gate returns to its initial position.
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
Decoupling busbar sections
2
Push the left-hand control gate to the left.
4
Remove the operating lever for the DISCONNECTING function.
The left-hand control gate returns to its initial position.
6
Switch the right-hand three-position disconnector to OPEN position
(insert the operating lever for the DISCONNECTING function and turn
180° counter-clockwise).
Operation