861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
• Minimum requirements of lifting rods:
- Material 42CrMo4 / AISI 4140 1.7225
- Diameter 30 mm
- Length of lifting rod for a single panel 1000 mm
- Length of lifting rod for a double panel 1600 mm
- Increase the length of the lifting rod by + 600 mmfor each further panel
- Certified lifting rods may be procured from the local Siemens representative.
• Chain with transport shackles
• Step-ladder
• Cable drum
• Guide string
• Rod magnet with flexible shaft
• Mirror with flexible shaft (welding mirror)
• Vacuum cleaner with flexible, thin tube and plastic tip
19.4

Overview of busbar housing covers with desiccant bags

Property damage
If busbar housing covers are removed from the switchgear, ensure that the correct cover
type is refitted on the busbar housing.
➭ Mark the cover type before removal.
➭ Verify that the correct cover type is refitted on the correct busbar housing.
Property damage
The busbar housing post insulator cover is marked with the designation "Busbar
direction". The marking must always point towards the busbars when the cover is
mounted.
➭ Observe the correct mounting position of the busbar housing post insulator cover.
Type of housing cover
Busbar housing cover without desiccant bag
holder
Busbar housing cover with desiccant bag
holder for 2x 250 g desiccant bags
Adhesive label: Filter
NOTICE
NOTICE
Front view
Installation
Rear view
47/214