Installation
Welded joint of the
standard design
Welded joint of the
aseismic design
Stipulations for the
foundation
Stipulations for evenness
and straightness
44/214
Weld the standard design diagonally to the foundation rails at 2 points. A floor fixing profile is
not necessary.
The welded seams must conform to the strength of an equivalent bolted joint with M10 bolts.
Fig. 26:
Welding seams of the standard version
Fixing points (26x45 mm)
Weld the aseismic design to the foundation rails at all 4 points. A floor fixing profile is not
necessary.
The welded seams must conform to the strength of an equivalent bolted joint with M10 bolts.
Fig. 27:
Welding seams of the aseismic design
Fixing points (26x45 mm)
Observe the following items when preparing the foundation:
• Dimensions of the floor opening and fixing points of the switchgear frame
(see page 43, "Constructional data of the foundation").
• Align the base frame of the switchgear starting from a fixed point.
• Determine level differences between the installation surfaces of the panels using
a measuring sheet, and compensate with shims (0.5 - 1.0 mm).
Evenness/straightness tolerance according to DIN 43661: 1 mm for 1 m length, 2 mm over
the width of the complete switchgear.
Fig. 28:
Measuring sheet for the foundation
Width of complete switchgear
1625 mm