Operation
1
Initial situation
3
➭
Push the interrogation lever downwards.
5
➭
Switch the left-hand three-position disconnector from READY-TO-
EARTH to OPEN position (insert the operating lever for the READY-TO-
EARTH function and turn 180° counter-clockwise).
174/214
De-earthing the busbar section in the right-hand panel
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Open the circuit-breaker to de-earth the right-hand panel.
4
➭
Push the left-hand control gate to the right.
6
➭
Remove the operating lever for the READY-TO-EARTH function.
The interrogation lever and the left-hand control gate return to their initial
position.