Siemens 8DA10 Series Installation And Operating Instructions Manual page 174

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Operation
1
Initial situation
3
Push the interrogation lever downwards.
5
Switch the left-hand three-position disconnector from READY-TO-
EARTH to OPEN position (insert the operating lever for the READY-TO-
EARTH function and turn 180° counter-clockwise).
174/214
De-earthing the busbar section in the right-hand panel
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
Open the circuit-breaker to de-earth the right-hand panel.
4
Push the left-hand control gate to the right.
6
Remove the operating lever for the READY-TO-EARTH function.
The interrogation lever and the left-hand control gate return to their initial
position.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents