7
➭
Switch the left-hand three-position disconnector to READY-TO-EARTH
position (insert the operating lever for the READY-TO-EARTH function
and turn 180° clockwise).
9
➭
Close the circuit-breaker to earth busbar section 2.
➭
Lock the circuit-breaker.
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
8
➭
Remove the operating lever for the READY-TO-EARTH function.
The interrogation lever and the left-hand control gate return to their initial
position.
Operation
173/214