Verification of safe isolation from supply

The following descriptions do not substitute reading the manufacturer documentation.
➭ Before using the voltage detecting systems, read the supplied manufacturer
documentation.
The following descriptions do not substitute reading the manufacturer documentation.
➭ Before using the voltage detecting systems, read the supplied manufacturer
documentation.
Mounting locations for voltage indicator and voltage detecting system
Example: Circuit-breaker panel 2300 A
39.1

LRM plug-in sockets

Hazardous voltage
Will cause death, serious injury or considerable property damage.
Verify safe isolation from supply.
➭ Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
➭ Test the function of the voltage indicator and the coupling section in accordance with
national standards:
- On a live panel
- With a test unit according to IEC 61243-5/EN 61243-5
- On all phases
➭ Use only voltage indicators or devices according to EN 61243-5 / IEC 61243-5 /
VDE 0682-415 to test the function of the coupling section. The interface conditions have
not changed as against the old standard VDE 0681 Part 7; the corresponding indicators can
still be used.
➭ Perform repeat test of interface conditions at the capacitive interfaces, as well as on
the indicators according to the customer's specifications or national standards.
➭ Do not use short-circuiting jumpers as separate plugs. The function of the surge arrester
installed is not provided if short-circuiting jumpers are used.
INFORMATION
INFORMATION
Voltage indicator /
voltage detecting system at the busbar
(option)
Voltage indicator /
voltage detecting system at the panel connection
(standard)
DANGER
Operation
197/214