861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
25.1

Removal of voltage transformers type 4MT3 from the busbar

Fig. 138: 4MT3 busbar voltage transformer
(shown without cover)
➭ Isolate and earth the busbar.
➭ Verify safe isolation from supply.
➭ Remove the low-voltage plug connector at the voltage transformer.
➭ Remove the cover of the voltage transformer.
➭ Remove the fixing bolts of the adapter plate.
➭ Screw four press-out bolts into the holes provided for this purpose in the adapter plate.
➭ Press the voltage transformer out of the bushing together with the adapter plate with the
help of the press-out bolts. While doing so, screw the press-out bolts in uniformly, so that
the transformer is not canted.
Fixing bolts at the adapter plate
4MT3 voltage transformer
Low-voltage plug connector
Adapter plate
Voltage transformer mounting plate
Busbar housing
Distance sleeves
Outside-cone bushing
Hole with setnut for press-out bolts
Holes with setnuts for press-out bolt