Siemens 8DA10 Series Installation And Operating Instructions Manual page 183

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
Disconnecting the voltage transformers from the busbar
1
Initial situation
3
Switch the three-position disconnector to OPEN
position (insert the operating lever for the
DISCONNECTING function and turn 180° counter-
clockwise).
Earthing the voltage transformers
1
Initial situation
3
Switch the three-position disconnector to EARTHED
position (insert the operating lever for the READY-TO-
EARTH function and turn 180° clockwise).
2
Push the control gate to the left.
4
Remove the operating lever for the
DISCONNECTING function.
The control gate returns to its initial position.
2
Push the control gate to the right.
4
Remove the operating lever for the READY-TO-
EARTH function.
The control gate returns to its initial position.
Operation
183/214

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents