861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
➭ Bolt the bus sectionalizer housing together with the pole supporting plate using bolt-and-
washer assemblies, conical spring washers, insulating washers and insulating sleeves M8.
Tightening torque: 20 Nm.
➭ Remove the 2 housing covers from the bus sectionalizer. Keep all bolt-and-washer
assemblies and nuts for later reuse.
➭ Undo the 2 hexagon head bolts and conical spring washers from the bus sectionalizer
busbar. Keep the bolting material for later reuse.
➭ Push the bus sectionalizer busbar into the bus sectionalizer housing and fasten it to the
contact studs on both sides using one hexagon head bolt M16x40 and conical spring
washer each. Tightening torque: 130 Nm.
Fig. 153: Bus sectionalizer busbar for 1250 A version
Installation
Pole supporting plate
Sealing ring (O-ring)
Bolt-and-washer
assembly M8 with
conical spring washer,
insulating washer and
insulating sleeve
Contact stud
Bus sectionalizer housing
Bus sectionalizer busbar
Hexagon head bolt
Conical spring washer