Operation
Indication WEGA 1.2C
L1
L2
L3
A0
A1
A2
A3
A4
A5
A6
A7
1
LED does not light up,
200/214
39.3

WEGA indications

Life-endangering high voltage
Risk of death, injury or considerable property damage. Verify safe isolation from supply
unambiguously.
➭ Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
➭ Use only voltage indicators or devices according to EN 61243-5 / IEC 61243-5 /
VDE 0682-415 to test the function of the coupling section. The interface conditions have
not changed as against the old standard VDE 0681 Part 7; the corresponding indicators can
still be used.
Fig. 216: Operating elements WEGA
WEGA 2.2C
L1
L2
L3
State of the
relay contacts
Red
U ≠ 0
U ≠ 0
U ≠ 0
U ≠ 0
U ≠ 0
U ≠ 0
U ≠ 0
U ≠ 0
LED lights up
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
DANGER
Description of the indication
1
Green
U = 0
• Operating voltage not present.
U = 0
• Operating voltage present.
• Integrated repeat test passed.
U = 0
• Operating voltage not present.
U = 0
• Failure of the operating voltage at phase L1
• Operating voltage present at phases L2 and L3.
• Integrated repeat test passed (L2 and L3).
U = 0
• Voltage present, current monitoring of coupling section below
limit value.
U = 0
If "Display Test" button is pressed:
• Display test passed.
U = 0
In operation:
• Voltage present and integrated repeat test passed.
• Voltage signal too high.
U = 0
• Auxiliary voltage missing.
Display (illuminated for WEGA 2.2C)
LEDs green and red
(state of the relay contacts)
Test socket L1
Test socket L2
Test socket L3
Earth socket
"Display Test" button