ABB GOE 2600 Installation And Commissioning Manual page 35

Transformer bushing
Table of Contents

Advertisement

Procedure
1.
Lower the bushing into the transformer.
2.
Install the winding cables to the fixed bottom
contact.
3.
Install the washers and nuts. Tighten the nuts in a
crosswise sequence.
Installation and commissioning guide
1ZSC000563-AAF EN, REV. 4, 2021-06-23
CAUTION!
Do not damage the stud bolts on the
transformer. There is a risk of metal
falling into the transformer.
NOTE!
Plastic sleeves put on two or three of
the stud bolts will help to guide the
flange, and will prevent damage to the
stud bolts.
CAUTION!
Make sure that there is no tension in
the winding cables. Tension in the
winding cables will cause damage to
the cables.
Torque
Please refer to the transformer
documentation.