Mechanical Loading - ABB GOE 2600 Installation And Commissioning Manual

Transformer bushing
Table of Contents

Advertisement

List of bushings applicable to this installation guide
Type
GOE 2600
GOE 2600

2.2.2 Mechanical loading

Maximum permitted static load on the outer terminal
The load must be applied below the midpoint of the outer terminal. The total cantilever load must be
perpendicular to the bushing axis. The bushing installation angle can be 0° – 30° from vertical.
NOTE!
The loads described in this section are static loads, for dynamic loads such as earthquakes and
extreme wheather conditions, please contact your Hitachi ABB Power Grids sales representative.
A.
Maximum cantilever load at installation angle 0°
B.
Maximum axial static load
C.
Load applied at the midpoint
Type
GOE 2600
Maximum permitted torque on the outer terminal
The maximum torque that is permitted on the outer terminal is 250 Nm.
Installation and commissioning guide
1ZSC000563-AAF EN, REV. 4, 2021-06-23
Test load 1 minute
Maximum cantilever load in operation
(N)
at installation angle (N)
9500
2500
Article number
LF121085-D
1ZSC902110-AAA
>0°
On request.
Maximum axial
static load (N)
20000
11