Toshiba Q9 Plus Bypass ASD Installation & Operation Manual page 235

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

As the three kinds of timbre mode (f312=1, 2, 3) are prepared, the proper mode can be selected to
fit the load condition.
If f300 is set to 8.0 kHz or more, the random mode function will not be performed, because the level of
motor magnetic noise is low at high carrier frequencies.
Note 3: When the PWM carrier frequency is high, selecting "Carrier frequency without reduction" causes the
inverter to be tripped more easily than selecting "Carrier frequency with automatic reduction."
De-rating of rated current
[240V class]
In case of aul=1 (Constant torque characteristic (150%-60s)) setting.
VFS15-
Ambient
VFS15S-
temperature
40°C or less
2002PL-W
40 ∼ 50°C
50 ∼ 60°C
40°C or less
40 ∼ 50°C
2004 PM/L-W
50 ∼ 60°C
40°C or less
2007 PM/L-W
40 ∼ 50°C
50 ∼ 60°C
40°C or less
40 ∼ 50°C
2015 PM/L-W
50 ∼ 60°C
40°C or less
2022 PM/L-W
40 ∼ 50°C
50 ∼ 60°C
40°C or less
2037PM-W
40 ∼ 50°C
50 ∼ 60°C
40°C or less
40 ∼ 50°C
2055PM-W
50 ∼ 60°C
40°C or less
2075PM-W
40 ∼ 50°C
50 ∼ 60°C
40°C or less
40 ∼ 50°C
2110PM-W
50 ∼ 60°C
40°C or less
2150PM-W
40 ∼ 50°C
50 ∼ 60°C
PWM carrier frequency
2.0k~4.0kHz
4.1k~12.0kHz
1.5 A
1.5 A
1.5 A
1.2 A
1.2 A
1.1 A
3.3 A
3.3 A
3.3 A
2.6 A
2.6 A
2.5 A
4.8 A
4.4 A
4.8 A
3.5 A
3.8 A
3.3 A
8.0 A
7.9 A
8.0 A
7.9 A
7.6 A
6.3 A
11.0 A
10.0 A
11.0 A
10.0 A
10.5 A
8.0 A
17.5 A
16.4 A
17.5 A
16.4 A
16.6 A
13.1 A
27.5 A
25.0 A
27.5 A
25.0 A
26.1 A
20.0 A
33.0 A
33.0 A
33.0 A
33.0 A
31.4 A
26.4 A
54.0 A
49.0 A
54.0 A
49.0 A
51.3 A
39.2 A
66.0 A
60.0 A
66.0 A
60.0 A
62.7 A
48.0 A
F-55
E6581611
12.1k~16.0kHz
1.5 A
1.2 A
1.1 A
3.3 A
2.6 A
6
2.5 A
4.2 A
3.4 A
3.2 A
7.1 A
7.1 A
5.7 A
9.1 A
9.1 A
7.3 A
14.6 A
14.6 A
11.7 A
25.0 A
25.0 A
20.0 A
29.8 A
29.8 A
23.8 A
49.0 A
49.0 A
39.2 A
54.0 A
54.0 A
43.2 A