Output parameters
Communication
Function
Title
No.
0667
Integral input
power pulse
output unit
0668
Integral input
power pulse
output width
0669
Logic output/pulse
train output
selection (OUT)
0676
Pulse train output
function selection
(OUT)
0677
Maximum numbers
of pulse train
output
0678
Pulse train output
filter
0679
Pulse train input
filter
0681
Analog output
signal selection
0684
Analog output
filter
0691
Inclination
characteristic of
analog output
0692
Analog output bias
0693
Factory specific
coefficient 6E
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
-
-
0: 0.1kWh
1: 1kWh
2: 10kWh
3: 100kWh
s
0.1/0.1
0.1-1.0
-
-
0: Logic output
1: Pulse train output
-
-
0: Output frequency
1: Output current
2: Frequency command value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100% equivalent)
16: Fixed output 2
(output current 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: Communication data
19: -
20: VIC input value
21, 22: -
23: PID feedback value
kpps
0.01/0.01
0.50-2.00
ms
1/1
2-1000
ms
1/1
2-1000
-
-
0: Meter option (0 to 1 mA)
1: Current (0 to 20 mA) output
2: Voltage (0 to 10 V) output
ms
1/1
2-1000
-
-
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
%
0.1/0.1
-1.0-+100.0
-
-
-
K-19
E6581611
Default
User
Reference
setting
setting
1
6.33.1
0.1
0
6.33.2
0
0.80
64
2
6.10.5
0
5.1
6.33.3
2
1
0.0
-
* 3