Toshiba Q9 Plus Bypass ASD Installation & Operation Manual page 401

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

 Table of output terminal functions 2
Function
Code
No.
30
POLR
Braking resistor overload pre-alarm
31
POLRN
Inversion of braking resistor overload pre-
alarm
40
RUN
Run/stop
41
RUNN
Inversion of run/stop
42
HFL
Serious failure
43
HFLN
Inversion of serious failure
44
LFL
Light failure
45
LFLN
Inversion of light failure
50
FAN
Cooling fan ON/OFF
51
FANN
Inversion of cooling fan ON/OFF
52
JOG
In jogging operation
53
JOGN
Inversion of in jogging operation
54
JBM
Operation panel / terminal block operation
55
JBMN
Inversion of operation panel/terminal block
operation
56
COT
Cumulative operation time alarm
57
COTN
Inversion of cumulative operation time alarm
58
COMOP
Communication option communication error
59
COMOPN
Inversion of communication option
communication error
60
FR
Forward/reverse run
61
FRN
Inversion of forward/reverse run
62
RDY1
Ready for operation 1
63
RDY1N
Inversion of ready for operation 1
64
RDY2
Ready for operation 2
65
RDY2N
Inversion of ready for operation 2
68
BR
Brake release
69
BRN
Inversion of brake release
70
PAL
Pre-alarm
71
PALN
Inversion of pre-alarm
78
COME
RS485 communication error
79
COMEN
Inversion of RS485 communication error
*2: At trip , , , , , , , , , , ~, ~, , ,
, ~, , , , , ~, , , , , .
Function
ON: 50% or more of calculated value of  set
overload protection level
OFF: Less than 50% of calculated value of  set
Inversion of POLR
ON: While operation frequency is output or DC braking is in
operation ()
OFF: Operation stopped
Inversion of RUN
ON: At trip *2
OFF: Other than those trip above
Inversion of HFL
ON: At trip (~, ~, , ~, )
OFF: Other than those trip above
Inversion of LFL
ON: Cooling fan is in operation
OFF: Cooling fan is off operation
Inversion of FAN
ON: In jogging operation
OFF: Other than jogging operation
Inversion of JOG
ON: At terminal block operation command
OFF: Other than those operation above
Inversion of JBM
ON: Cumulative operation time is  or more
OFF: The cumulative operation time is less than 
Inversion of COT
ON: Communication error of communication option occurs
OFF: Other than those above
Inversion of COMOP
ON: Reverse run
OFF: Forward run
(Operation command state is output while motor operation is
stopped. No command is to OFF.)
Inversion of FR
ON: Ready for operation (with ST / RUN)
OFF: Other than those above
Inversion of RDY1
ON: Ready for operation (without ST / RUN)
OFF: Other than those above
Inversion of RDY2
ON: Brake exciting signal
OFF: Brake releasing signal
Inversion of BR
ON: One of the following is turned on
ON POL, POHR, POT, MOFF, UC, OT, LL stop, COT,
and momentary power failure deceleration stop.
Or , , ,  issues an alarm
OFF: Other than those above
Inversion of PAL
ON: Communication error occurred
OFF: Communication works
Inversion of COME
K-35
Action
overload protection level
E6581611
Reference
6.19.4
7.2.2
6.29.11
6.14
6.2.1
6.29.12
6.38
7.2.2
11
6.22
7.2.2
6.38

Advertisement

Table of Contents
loading

Table of Contents