Toshiba Q9 Plus Bypass ASD Installation & Operation Manual page 301

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

[Parameter setting]
Title
Function
Logic output/pulse train
f669
output selection (OUT)
Pulse train output function
f676
selection (OUT)
Maximum numbers of
f677
pulse train output
f678 Pulse train output filter
Digital panel meter for reference
Type: K3MA-F (OMRON)
Connection terminal: OUT-E4, NO-E5
Note 1: When item of f676 reaches "Reference of max. value", the number of pulse train set by f677
are sent to output terminals (OUT)
Note 2: The ON pulse width is maintained constant.
The ON pulse width is fixed at a width that causes the duty to reach 50% at the maximum pulse
number set with f677.
Therefore, the duty is variable.
For example, the ON pulse width is
Note 3: The minimum pulse output rate is 10pps. Keep in mind that no pulses can be put out at any rate
smaller than this.
Note 4: f676 = 12 is the motor drive frequency.
Adjustment range
0: Logic output
1: Pulse train output
0: Output frequency
1: Output current
2: Frequency command value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12:Stator frequency
13:VIA input value
14:VIB input value
15:Fixed output 1
(output current 100% equivalent)
16:Fixed output 2
(output current 50% equivalent)
17:Fixed output 3
(Other than the output current)
18:Communication data
19: -
20: VIC input value
21, 22: -
23: PID feedback value
0.50-2.00 (kpps)
2-1000 (ms)
approximately 0.6 ms when f677= 0.80 (pps)
approximately 0.5 ms when f677= 1.00 (pps)
approximately 0.3 ms when f677= 1.60 (pps)
F-121
E6581611
Reference
Default
of maximum
setting
value of
f677
0
fh
185%
fh
150%
150%
185%
185%
250%
-
100%
100%
100%
fh
0
10 V
10 V
6
185%
185%
100%
100.0%
-
20mA
-
100%
0.80
64