Toshiba Q9 Plus Bypass ASD Installation & Operation Manual page 317

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

Settings for speed command via communication
Title
Function
Frequency setting mode
fmod
selection
Communication function parameters (2-wire RS485 communication)
Communication speed, parity, inverter number, and communication error trip time settings can be changed
via panel operations or communication.
[Parameter setting]
Title
Function
Baud rate
f800
f801
Parity
Inverter number
f802
Communication time-out time
f803
*1
Communication time-out action
f804
*1
f805 Communication waiting time
Setting of master and slave for
f806
communication between inverters
Communication time-out
f808
detection condition
Communication command point
f810
selection
Communication command point 1
f811
setting
Communication command point 1
f812
frequency
Communication command point 2
f813
setting
Communication command point 2
f814
frequency
Selection of communication
f829
protocol
Adjustment
range
0 - 14
0 (Setting dial 1)
Adjustment range
3: 9600bps
4: 19200bps
5: 38400bps
0: No parity
1: Even parity
2: Odd parity
0-247
0: Disabled
0.1-100.0 (s)
0: Alarm only
1: Trip (Coast stop)
2: Trip (Deceleration stop)
0.00-2.00
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in
case the master inverter fails)
2: Slave (Emergency stop tripping
in case the master inverter fails)
3: Master (transmission of
frequency commands)
4: Master (transmission of output
frequency signals)
0: Valid at any time
1: Communication selection of
fmod or cmod
2: 1 + during operation
0: Disabled
1: Enabled
0-100
0.0-fh
0-100
0.0-fh
0: Toshiba inverter protocol
1: Modbus RTU protocol
F-137
E6581611
Standard
Setting example
defaults
4 (RS485
communications)
Default setting
4
1
0
0.0
0
0.00
0
1
0
0
0
100
*2
0
6

Advertisement

Table of Contents
loading

Table of Contents