6.29.10 Over-torque trip
f615 : Over-torque trip/alarm selection
f616 : Over-torque detection level
f618 : Over-torque detection time
f619 : Over-torque detection hysteresis
• Function
f615=0: No tripping. (Failure signal FL not activated)
f615=1: The inverter trips when a torque exceeding the f616-specified level has been detected for
6
[Parameter setting]
f615
f616
f618
f619
Note: f618= 0.0 seconds is the shortest time detected on control.
If the torque value exceeds the value set at f616 and doesn't return below f616-f619
for a time that exceeds the value set at f618, tripping or output alarm will be activated.
ot is displayed in the event of a trip.
An over-torque alarm can be put out by setting the output terminal function selection parameter.
longer than the f618-specified time. (Failure signal FL activated)
Title
Function
Over-torque trip/alarm selection
Over-torque detection level
Over-torque detection time
Over-torque detection hysteresis
Adjustment range
0: Alarm only
1: Tripping
0 (disabled),
1-250 (%)
0.0-10.0 (s)
Note
0-100 (%)
F-108
E6581611
Default setting
0
150
0.5